Table of Contents

I. Installation...............................................................................................3

II. Operation principle................................................................................13

III. Explosive views and spare parts lists.....................................................14

IV. Wiring diagrams..................................................................................21

V. The specifications on common software functions for inverter AC..............25

VI. Failure display......................................................................................43

VII. Reference of the fault code and detecting methods for inverter...............48

VIII. User's Manual for Split Wall-Mounted Air Conditioner.............................56

I .Installation

1. Safe Codes 1)The service supplier shall urge its service people to take effective human safety measures during operation.

2)The service people shall select an installation position that is solid, unlikely shocked and able to support the weight of machines.

3)To avoid fire, the installation position shall be away from the place where flammable gas exists.

4)When the outdoor unit is installed or relocated on the 2nd floor of a building or at a height over 2m, the service people must use the rope with adequate strength to fasten the outdoor unit securely (or take other safety measures) to prevent the machine from falling down.

5)For working on height, anti-fall measures shall be taken for the tools and materials used outside the building.

6) After completion, the installation people must carry out electrical safety inspection. The electrical wiring must be in conformance to the national or local safety standards to ensure no leakage.

7)If it is needed to refit the power supply during installation, approval must be obtained from the user and the operation must be carried out by the people qualified for electrical safety. The result must be in conformance to the national or local standards on electrical safety.

8)The service people must check each position of the casing during test run. In case of electric leakage, immediately stop the machine and check it. If it is the problem of installation, solve it and test again. Ensure the air conditioner works normally. If it is the problem of air conditioner, report it to the vendor.

9)During installation, if the service people find that the user's power supply has the potential safety problem, they must notify the user and record the details on the warranty card for confirmation, or take corrective actions.

10)Before completion of the installation or during removal or installation of the machine, it is prohibited to switch on the power and start the machine, in order to avoid safety accidents.

11)The service people must follow the national or local safety rules when using the welding tools. The welding must be performed by the people with safe operation qualification.

12)CHIGO has the right to supervise the service supplier for its work safety. The accidents due to the service supplier's fault shall be the service supplier's responsibility.

13)During installation, the service people shall take care to avoid skid, cutting, scratch, burn, electric shock or fall. Take care to protect the eyes during welding.

14) After installation, ensure that the people or objects are away from the machine before you connect the power supply. Do not switch on the power or test the machine until the power supply is correctly connected.

2. Preparation of installation tools

Table: Configuration of Installation Tools

Tool 1. Impact drill, with O70mm bit 1 pc 2. Bit, O10mm or O12mm 1 pc 3. Slotted screwdriver and cross screwdriver, 1 pc for each (mini slotted screwdriver) Slotted: 100 or 120mm; Cross: 120 or 145mm 4. Torque wrench (2 pcs), spanner (3 pcs) Spanner: 8?10, 10?12, 12?14mm 5. Hammer (1 pc) 0.5Kg 6. Electrical knife (1 pc) 7. Wire stripper (1 pc) 8. Sharp nose pliers and cutting pliers (1 pc for each) Cutting pliers: 150mm 9. Pipe bender (1 set) 10. Pipe expander (1 set) For the expanding the opening of the added pipe 11. Pipe cutter (1 pc) For cutting the excess copper tube) 12. Reamer (1 pc) For deburring the copper tube 13. File (1 pc) 150 or 200mm 14. Multimeter (1 set) Level 5.0 15. Leakage detector or soap / sponge (1 pc) For detecting if there is leakage at the connection 16. Thermometer or digital temperature meter (1 pc) For measuring the temperature of the intake and outlet air of the air conditioner 17. Pressure gauge For measuring the working pressure of the air conditioner system 18. Level gauge or plummet (1 pc) 19. Putty scraper (1 pc) 20. Hex wrench (1 set) 21. Electric probe 22. Safety belt 23. Rope (acc. to weight-bearing requirements) 24. Laying cloth, cover cloth, shoe covers, wiping cloth 25. Ladder and other requisite tools

Other auxiliary materials (depending on the site conditions)

Materials 1. Fixing support for outdoor unit GB/T5059GB/T5213 2. Expansion bolt 10mm (4 pcs) 3. Anchoring bolt (O10mm) (with spring washer) (4 pcs) 4. Concrete nail 5. Heat insulation strap 6. Insulation tape 7. Gypsum powder (1 bag) 8. Copper tube and power cable 9.PVC pipe (optional) 10. Square channel (optional) For fixing the connection pipes and wires 11. Others

3.Check the machine (whether the appearance is in good condition, and whether the accessories are complete)

Machine Inspection Focus on checking the single cooling, double temperature and cooling capacity whether conform to the specifications, in terms of the indoor and outdoor units are compatible, and the style of indoor unit conforms to the requirements.

Look through the observation hole, and check whether the connection pipes, remote controller, Product Warranty Card and other accessories are complete. If not, do not open the package but contacting the vendor.

4. Check the user's power supply (kilowatt-meter capacity, wire diameter, electric leakage protection switch, ground wire and voltage)

Check the power supply Use the multimeter to measure the power voltage, which shall be within +/-10% of the rated voltage. Use special line for the power supply of air conditioners, and ensuring that the capacity of entire supply line (branch line, power line, kilowatt-meter, air switch, etc) is higher than the maximum rated current of air conditioner. The power configuration and cable distribution must meet the local requirements for electrical safety. Advise the user to apply special air switch, electric leakage protector and other necessary protection devices for air conditioners. Their capacity shall meet the needs of air conditioner. For the line with fuse, it is prohibited to use copper wire to replace the fuse.

Table: The Requirements of Different Models for Power Supply

Table 1 (220V-240V)

Item

Model Section Area of Power Cable (mm2) Circuit Switch (A) Split Wall-Mounting Series 25 1.0 10 30, 32, 35, 36 1.5 10 51, 61 1.5 10 66 2.5 20 25 Auxiliary electric heater 1.5 10 32, 35, 36Auxiliary electric heater 1.5 10 51, 61, 66 Auxiliary electric heater 2.5 20

5 .Selection of Installation Position (Indoor / outdoor lens sequence needs adjustment)

Requirements for Installation Position The installation shall be operated at the place which is solid, unlikely subject to shock and able to bear the weight of machine. The outdoor unit shall be installed at the place which with good ventilation, and unlikely subject to rain or direct sunshine. Ensuring that the air conditioner can be easily accessed for maintenance and repair. Keep the indoor and outdoor units as close as possible. The connection pipe shall be short as it might be. To facilitate the air flow, keep adequate space around the indoor and outdoor unit, and avoid flammable or corrosive gas nearby. The drainage shall not affect the constructions of dwellers underneath or the user himself. The machine shall be kept 2m or more away from the electric appliances and heat source. Avoid TV set, sound box, computer and other deluxe home appliances below the indoor unit. The indoor unit shall be able to blow the cold and hot air evenly to everywhere of the room. According to the power supply mode (powered by indoor or outdoor unit) and the length of power cable, select the position which close to the power supply, in order to facilitate the connection of power line. Moreover, ensuring that it is not needed to extend the power cable and selecting a position beyond reach of children. Determination of Installation Position Select the final position of indoor and outdoor unit according to the requirements above (Mark properly if needed).

6 .Execution of Installation

Installation of Wall-mounted indoor unit Unpack the machine and take out the accessories, wall-mounting plate and remote controller. Mount the bundled batteries into the remote controller and observe for abnormality. Before installation, make sure to energize the indoor unit and test it by using the remote controller. Observe the fan and swing louver for their working conditions. If any abnormality occurs, adjust immediately and install again. Fix the wall-mounting plate according to the selected position of indoor unit and the route of the pipe.

Firstly, use a steel nail to fix the wall-mounting plate onto the wall. Level it with the level gauge and then fix tightly.

Note: When installing the models with additional functions (purification device), we shall take the position of this device into consideration for the distance to the ceiling.

Select the position of wall-cross hole according to the position of wall-mounting plate.

Selection of piping mode: Try not to choose the mode of right exit-pipe so as to ensure the orderliness and smoothness of the pipe.

1. Route the pipe directly along the right side of the machine body. 2. Route the pipe directly on the rear. When bending the pipe, please support the elbow with your right hand and then use your left hand to rotate slightly for 90° before stop. 3. Route the pipe along the left side. This step is the same as the above step. The only difference is that the bending angle is higher than that in the previous step, that is, it should be bent to 180°. Take care to rotate this angle slightly and slowly; Otherwise the pipe would be flattened easily . Then, drill a hole (shuld be a little larger than the outer diameter of the wall-cross tube so as to ensure the wall-cross rube can be inserted through). Caution: For easy drainage of the water out of the internal unit, the indoor unit shall be mounted slightly higher than the wall-cross hole. Meanwhile, the wall-cross hole must be inclined outward down.

Make sure to take dustproof measures when drilling holes with the impact drill. Hang the indoor unit onto the clamp of the wall-mounting plate. Move the body of indoor unit left and right, and check if it is fixed tight. When multiple indoor units are to be installed in one room (e.g. guest hall, meeting room, restaurant, etc.), full consideration should be made to the integral appearance and working performance. They should be installed on the same level (with the upper as the benchmark) and keep a certain distance, thus to ensure that the working performance of each indoor unit will not be affected. Installation of Outdoor Unit

1. To install the outdoor unit onto the wall, use the bit of fixed depth to drill holes according to the selected position, but take care to avoid the wall clearance. Firstly, mount an expansion bolt 10x100 (mm). Then, use the rope to move the support outdoors and make a simple fixing. Calibrate the level with level gauge and mark out the other positioning holes. Then, remove the support and use the impact drill with fixed depth bit to drill the other fixing holes of the support. Finally, fix the support onto the exterior wall. 6 pcs required for model 61 or lower, and 8 pcs required for the model over 61.

Note: The expansion tube of the expansion screw must be fully punched into the wall. 1. Move the outdoor unit out of the room and put it onto the support with care. Fix with 4 bolts O10mm. (Note: The installation people working on the 2nd floor or higher must wear safety belt. The outdoor unit must be tied securely with rope before it can be put outdoors. Take anti-fall measures to avoid accident. )

2. The outdoor unit is directly onto the ground (e.g. balcony, roof platform, outdoor ground of the 1st floor, and other platforms that can accommodate the outdoor unit adequately). According to the size of chassis mounting hole, select proper expansion screws to fix tightly. The height difference between indoor and outdoor unit shall not be higher than 5m; otherwise it might cause difficulty to oil return and affect the service performance.

Installation Requirements for Multiple Units

1. To install multiple units on the same wall or on the same direction of a building, all the machines on one floor should be installed on the same level (based on the level of machine leg), and the transverse spacing shall be kept at least 60cm or more, as long as the machine performance will not be affected.

2. If there are multiple units on different floors on the same wall or the same direction of the building, they should be preferably installed on the same vertical line (based on the left side of the body streamline). To avoid air return or mutual interference at the outlet, the longitudinal spacing shall be kept at least 65cm or more. Requirements for outdoor guardrail (optional): If the user is to install guardrail for the outdoor unit, the spacing to the machine body must be kept 0.5m or more.

Insert through Pipe Bundle the connection wire to the connection pipe and drainage pipe. (The connection wire may also be inserted through PVC pipe) To insert through the pipe, protective measures should be taken to prevent the expanded bell mouth from damage and prevent the sand from entering the connection pipe. Connect to Machine Take a connection pipe with expanded mouth, coat frozen oil evenly onto the connector of the 2-way / 3-way valve and the expanded mouth . Put the expanded mouth and connector on the same straight line and rotate the nut to its end with hands, and tighten it with spanner. Remove the end cover and clip of outdoor connection wire. Then, connect the wire to position according to color or mark indicated in the wiring diagram. When the exposed section is fully inserted, use the screw to press it tightly. Do not cut the round connector at the connection wire end into Y-shape. Fix the wire with clamp and then fix the end cover of the wire. Vacuumming After connecting the pipe between indoor and outdoor unit, it should be vacuumed with vacuum pump. Operate as follows:

Loosen the nut on low-pressure valve element and filling portal, connect the vacuum pump to the filling portal by hose with pin, and then start the vacuum pump. When the indicator gauge points to 15Pa, stop vacuumming and hold for approx. 30s. Pay attention to the vacuum level. If decreased, be sure to eliminate the leakage. Repeat the above procedures. When the vacuumming process is completed, close the vacuum valve and open the high-pressure valve element for 1/4 turn to fill the refrigerant to the low-pressure section. Remove the connection hose. Fully open the high-pressure and low-pressure valves . Tighten the nuts on the valves. Leakage Detection Use a sponge soaked with soap water or a leakage detector to check the connectors and access-valves on indoor and outdoor units. Keep testing for no less than 3 minutes at each position. When the leakage detection is completed, do wash away the residual soap water. (Notes: In summer, leakage detection should be done under stop state. In winter, it should be done under heating mode). )

Position Most Likely to Leak

Besides four connectors connecting outdoor pipes, nuts at high-pressure / low-pressure valve core and filling portal are most likely to leak but often neglected. Therefore, when installing the machine, make sure to fully open the valve core to dead position and tighten every nut and check for leakage. The connector with leakage problem should be reinstalled. Pipe Wrapping and Wall Hole Blocking Sort the pipeline in good order. Use pipe bender when bend the pipe with 90°. To avoid flattening or cracking the pipe without pipe bender, do bend it with a radius as large as possible.

Table: Standard of piping torque:

1. Nut torque of connecting pipe (R410a?R407c)

Outer diameter of copper pipe Torque mm inch Kg.f/m ?6.00 1/4 1.8 ?9.52 3/8 4.2 ?12.7 1/2 5.5 ?15.88 5/8 6.6 ?19.05 3/4 6.6 2. Nut torque of connecting pipe (R22)

Outer diameter of steel pipe Fastening torque Reinforced fastening torque mm inch Kgf/m Kgf/inch Kgf/m Kgf/inch ? 6.00 1/4? 1.6 6.3 2.0 7.9 ? 9.52 3/8? 3.0 11.8 3.5 13.8 ? 12.7 1/2? 5.0 19.7 5.5 21.6 ? 15.88 5/8? 7.5 29.5 8.0 31.5 ? 19.05 3/4? 12.0 47.2 14 55.1

Pipeline wrapping and wall-hole blocking Wrap the connection pipe and machine-connection wires together, water pipe shall be placed under the connection pipe and shall not be wounded and intersected, and it shall be wrapped from outdoor unit to indoor unit in case rainwater entered and had bad influence on temperature and insulation.

Heat insulation measures shall be adopted separately for the pipeline joint of the indoor unit. When the pipeline was wrapped, it shall be fixed on the wall by pipe clamps for every 1m distance. Block the wall-hole with plaster or putty with the machine, in case the rainwater and the wind entered. Meanwhile, make the blockage match the wall as possible. Inspection before machine testing Check if the internal wires of the unit are connected. It needs to be noted particularly that the wires shall be connected correspondingly; the grounding shall be reliable; and all the naked wires shall be pressed tightly. When the power was off, the insulating electric-resistance of the null line, the live wire and the ground wire of the plug shall be more than 2 megohm. Inspect whether the indoor and outdoor units are installed firmly. Make sure that all people or objectives are away from the machine, do check it's safe before turn the power on. Power supply connection Before installation and safety inspection, electrification is strictly forbidden. Power connection shall be in accordance to the region or country's safety requirments, and make sure that wires were firmly connected. Inspection for machine test When the power is on, turn on the machine by remote controller, and press every buttom to see if the machine responds. If the machine is a floor standing one, testing it with control panel is required. Inspect noise and vibration of the machine, if there are any abnormal phenomena, they shall be debugged or maintained. Inspect the drainage of the indoor unit. Pour a cup of water on the indoor unit evaporator and check the draining situation. Use remote controller (control panel when floor standing machine) to adjust the indoor fan to carry out switching of high, medium and low air speed, inspect whether the air swinging is flexible. Record the data of working voltage, current, system pressure, temperature, differences of inlet and outlet air etc. under modes of cooling and heating. In case of abnormal conditions such as smell, scorched flavor, smoking and so on, do stop the machine for inspection and solving it immediately. If problems caused by anything from the user, advices shall be given to improve.

. 7 .Introduction of usage and maintenance knowledge

Test of testing machine After start, setting cooling or heating mode according to the temperature. The installation personnel shall introduce the usage of the remote controller in detail to the user, including the function of every button, and how to judge the battery shall be changed and how to change. The power shall be cut and the battery of remote controller shall be taken out when the machine is not used for a long time. Introduce the method of disassembling and cleaning the filter net (replacing the air filter) to the user, and instruct them to operate until they are skillful. The outdoor unit shall be ventilated, so as to prevent sundries from blocking the condenser and influencing the heat dissipation. Users can inspect and clean the condenser and remove sundries when they can guarantee their safety, or they shall ask professionals for help.

8. Ending (clear the site, collect tools, fill the warranty card and say goodbye to the user)

End of work Hand over the instruction manual and accessories to the user. Collect the installation tools and do not ignore anything. Clean installation site, return the displaced articles and electric appliances.

Note:

After lengthening the connecting pipe, please compensate refrigerant according to the following table:

Unit (btu) 9000--12000 18000 24000-54000 Compensation value (g/m) 15 25 60

II. Refrigerant cycle diagram 1 .Cooling only

2.Heat pump mode

III. Explosive views and spare parts lists

1. indoor explosive view for 9k

Serial No Part Name Serial No Part Name 1 Louver 26 Copper pipe of sensor 2 Guide bearing 27 Right plate I 3 Connecting lever 28 Right plate II 4 Swing louver 29 Right plate III 5 Step motor 30 Motor platen 6 Rocker 31 Motor 7 Outlet part 32 Base accessory 8 Wire clip 33 Electric box cover 9 Base 34 Room temp . sensor 10 Guide water board 35 Tube temp . sensor 11 Cross flow fan 36 Electric control plate 12 Bearing 37 Transformer 13 Evaporator assembly 38 Connecting wire 14 Evaporator left plate 39 Electric box 15 Screw cover 40 C2 wire clip 16 GV middle frame 41 Terminal board 17 Clip 42 Power cord 18 GV left air filter 43 Connecting cable 19 Front panel assembly 44 Pipe clamp 20 Display lamp panel 45 Wall-mount frame 21 Display box 46 Step motor 22 GV right air filter 47 23 Middle frame cover plate 48 Thermal insulation pipe 24 Room temp. sensor holder 49 Remote controller 25 Sensor insert block 2 .indoor explosive view for 12k

Serial No Part Name Serial No Part Name 1 Louver 30 Spring of sensor 2 Thermal insulation pipe 31 Copper pipe of sensor 3 Swing louver 32 Evaporator right plate 1 4 Swing step motor 33 Evaporator right plate 2 5 Little connecting lever 34 Motor platen 6 Electric connecting lever 35 Tube temp. sensor 7 Louver support pole 36 Room temp. sensor 8 Water resistant ring 37 Electric control plate 9 Guide bearing 38 Transformer 10 Outlet part 39 Terminal board 11 Base 40 Wire clip 12 Cross flow fan 41 Electric box 13 Bearing 42 Indoor unit 14 Metal PTC electric heater 43 Power cord 15 Evaporator 44 Connecting cable 16 Evaporator plastic left plate 45 Pipe clamp 17 Screw cover 46 Step motor 18 Middle frame 47 Wall-mounting frame 19 Clip 48 Smoke filtrating device louver 20 Air filter 49 Smoke filtrating device front board 21 Display box 50 Dust connecting canister assembly 22 Display lamp panel 51 Journey switch 23 52 Smoke filtrating device step motor 24 53 Electric cover 25 54 Smoke filtrating device plank 26 Front panel 55 Electric needle 27 PMMA panel 56 High voltage bag 28 Middle frame cover plate 57 Fixed board assembly 29 Room temp. sensor holder 58 Remote controller

3. indoor explosive view for 18K?22k

Serial No Part Name Serial No Part Name 1 Louver 18 Electric box cover 2 Air outlet grill 19 Active board of electric box cover 3 Swing louver connecting lever 20 Evaporator assembly 4 Third wind motor 21 Screw cover 5 Connecting rod 22 Middle frame cover plate 6 Swing louver 23 Front panel 7 Outlet part 24 Air filter 8 Louver motor 25 Middle frame 9 Wall-mounting frame 26 Left plastic plate 10 Motor 27 Cross flow fan 11 Pipe clamp 28 Bearing of cross flow fan 12 Wire clip 29 Base 13 Electric box 30 Water pipe 14 Electric control plate assembly 31 Guide bearing 15 Transformer 32 PMMA panel 16 Terminal board 33 Display lamp panel 17 Motor platen 34 Display box 4. outdoor explosive view for 9k?12k

Serial NO part name Serial NO part name 1 Front grill 27 Outdoor PCB 2 Grill clip 28 Wire clip 3 Front panel 29 Terminal board 4 Left protect net 30 Wire clip 5 Nut 31 PU sponge 6 Gasket 32 Rear grill 7 Axial flow fan 33 Span pipe 8 Motor 34 Span pipe 9 Motor support 35 3-way pipe 10 PE sponge 36 Condenser 11 Base 37 4-way valve assy 12 Pillar 38 Intake pipe for the condenser 13 Anti-vibration pad for the compressor 39 Capillary assembly 14 Compressor 40 Damping rubber 15 Gasket 41 Filter 16 Nut 42 Right panel 17 Partition board 43 Large handle 18 Small handle 44 Valve installation plate 19 Top panel 45 High-pressure valve 20 Module radiator 46 Low-pressure valve 21 Radiator plate bolt 47 Screw 22 Radiator plate 48 Drainpipe for the condenser 23 Electric box 49 Discharge pipe 24 Outdoor module 50 Damping block 25 PFC module 51 Suction pipe 26 Sensor 52 Damping rubber 53 Connecting wire

5. outdoor explosive view for 18k?22k

Serial NO Part name Serial NO Part name 1 Top panel 12 High-pressure valve 2 Electric box 13 Compressor 3 Rear grill 14 Base 4 Partition board 15 Condenser 5 4-way valve 16 Motor support 6 Electric expansion valve 17 Motor 7 Desiccation filter 18 Axial flow fan 8 Right panel 19 Front grill 9 Large handle 20 Front plate 10 Valve installation plate 21 Left protect net 11 Low-pressure valve 22 Left panel

IV. Wiring diagrams (outdoor and indoor, zoom in when reading please)

1. 9k units

2. 12k units

3. 18k units 4. 22k units

V?The specifications on common software functions for inverter AC

1. Hardware requirements

1.1.Universal basic requirement

The power voltage's sphere of application:Alternating current..50/60Hz are compatible,to permit the voltage wave range:165V~265V or 100~130V?

The ambient temperature and humidity of using the PCB:-20?~85?,?=30%~95%;

1.2.Displaying lamp panel

(1) The displaying lamp panel schematic diagram and PCB size are determined by the different styles ?You can make reference to appendix 2 about the display screen and introductions.

(2) The models append function within double 8 nixietube:except turning off the units,the display screen will show brightness when the mainboard receives the correct remote controller's signal?If not receive the relevant signal after 30 seconds,the display screen's brightness will reduce to 30%;certainly, the models haven't the reducing brightness function without double 8 nixietube?

(3) The displaying lamp panel demands to use 2618/2668 driving motion,the hardware interface should be universal 6 bit port.

1.3.Controlling mainboard

(1) The PCB illustrative diagram is decided by the model style and the relevant internal kernel.

(2) The communication circuit of the indoor and outdoor should demand to adopt JG/SJ 12-2008?CHIGO frequency conversion air-conditioner indoor and outdoor controller communication rules??

2. Software function

2.1.The symbol and wind speed's definitions

(1) The symbol definition

Ts:the setting temp.

Tr:the indoor temp.

Tp:the indoor coil pipe temp.

(2) The wind speed definition

The indoor fan(PG motor)wind speed definition. Please refer to the following form 2-1.

Form 2-1 model mode Super high winds High winds Mid winds Low winds Slightly winds Any model cooling FS5 FS4 FS3 FS2 FS1 heating FS10 FS9 FS8 FS7 FS6 NOTE :(1)The FS1~FS10 are programmable dates,and they are in the EEPROM;

(2)The motor rotate-speed should refer to the motor parameter, if the indoor motor uses the tapped control.

2.2 basic mode

2.2.1 The automatic mode

1?the models with the universal remote controller

(1) the setting temperature is 25?,and it is unadjustable ?

(2) If press the "emergency switch" button on standby or use the remote controller to set the automatic mode ,the air-conditioner will enter the automatic operating mode,and its default setting temperature is 25??.

(3) when enter the automatic mode,the system will decide the corresponding running mode according to the indoor ambient temperature,please refer to form 2-3:

Form 2-3

Indoor temp. Tr "cancel" > "turbo"; when receiving the signal of the turbo button on the remote controller, the indoor "turbo lamp" will lighted immediately (when there is the "turbo lamp" on the display lamp board)?

(2) During the turbo operation, the compressor will operate at the current allowable maximum frequency point; the wind speed of the air conditioner is set at the "super high wind", at this moment, the wind speed on the remote controller although can be set, but it is ineffective for the air conditioner.;

(3) During the turbo operation, the user can set the operating status with pressing other buttons (except on/off and modes), the air conditioner will not refresh the turbo operating time any more when receiving the turbo code;

(4) Ending conditions of the turbo operation:

a) When the operating time is longer than 20 minutes, the turbo operation will be cancelled automatically.?

b) Cancel with the turbo button of the remote controller?

(5) It will operate according to the corresponding work frequency of cooling/heating when the turbo is automatically cancelled, while it will operate according to the setting mode of the remote controller when cancelled in the method of remote control?

(6) The turbo operation can be set under the status of timing turn-on, when it is the time of the fixed time, the turbo method will start running.?

(7) During the turbo operation, all conditions of limitation and protection will act?

2.4 Auxiliary function

2.4.1 Self- check function

(1) the indoor unit possesses self-checking function?firstly press the emergency switch button ,and then switch on the power supply,thus enter the self-check state,all the delivery outlets output the relevant information in turn:

Model code(0.5S)-the running lamp brighten(0.5S)-the timing lamp brighten(0.5S)-the turbo lamp brighten(0.5S)-the economical operation lamp brighten(0.5S)-the high bit of the digital tubes all brighten(0.5S)-the low bit of the digital tubes all brighten(0.5S)-the indoor fan starts (time lag 0.5s)- power supply outputs(outdoor relay electrifies for 0.5S)-the buzzer sends 1 sound like "di"(time lag 0.5S)-the buzzer sends the second sound and shows to end all the exports?

Remark: different types vary due to the difference between display lamp boards; the LED lamps and digital tubes will be lightened according to corresponding display.

(2) in self-check status ,the external air flap runs at closing motion, and the internal air flap operates at swing wind way?

(3) when the indoor fan starts,"the running lamp "indicates the indoor fan's feedback condition?If the running lamp flickers, it shows the feedback signal ,or else absence of feedback;quick twinkle shows the indoor fan runs at quick speed, or else low speed?

(4) model code: "25" stands for 25GW,"35" stands for 35GW,the rest may be deduced by analogy?

2.4.3 power-off memory function

EEPROM stores the running parameter before the air conditioner is shut down ,after power on again ,the air condition will return to the running status before power down?

(1) when the unit receives the correct remote control code in the starting up or standby status, The effective control code and data validation are checked and wrote in the designated unit EEPROM.?

(2) when turn on or turn off the unit with the emergency switch button,or press any buttons to set the air conditioner the relevant condition,thus the operation results will be key to control code written into the specified unit of EEPROM .

(3) timing time is renovated and stored in EEPROM every one hour,electrify again after power cut,the unit will run according to the timing time stored before power cut?

(4) because the sleeping function has not the operation timing turning off the unit , when have set the sleeping function,electrify again after power cut,the system will choose to turn on the unit , meanwhile doesn't memory sleeping function any more;shut down the unit because of malfunction,electrify again after power cut,the system will select turning on the unit ?

(5) power-off memory only memories the operating mode , but don't remember these auxiliary functions like turbo , highly efficiency, sleeping function and so on ?

2.4.4 Emergency switch function

Press the emergency switch button in the starting condition,the unit is shut down;vice versa,and its setting temp. is permitted to be 25??Press the emergency switch button every time, the buzzer sends one time sound?

2.4.5 Sound,light prompt function

(1) the controller possesses the buzzer?When it receives the order of the remote controller,and the system electrifies or shut down in the starting condition , the buzzer will send one "di" sound?

(2) when the system appears the malfunction,the nixietube or LED indicate the relevant fault or protection code?

(3) when Air Conditioning System is DC inverter Multi-Split Air-Conditioner Unit,if the indoor unit and outdoor unit appear the mode conflict,the indoor double 8 nixietube will display "DI"?

2.4.6 display shutting screen function (support the model with this function)

(1)when the air conditioner is starting,pressing the "LAMP" button on remote controller enter the display shutting screen function condition,shut all the indicator on the display lamp panel;press it again can exit the display shutting screen function,the display lamp panel display original status?

(2)when the unit receives the remote controller signal in the display shutting screen condition,the display lamp panel will show at the setting requirement,and then all the display lamp are shut after 10s?

(3)the system doesn't run this function in starting default status,After conversion mode automatically cancelled this function?

2.4.7 outdoor defrosting electrical heat tape function (support the model with this function)

When the ambient temperature is less 0?,the system will start the outdoor defrosting electrical heat tape function?

3 indoor common malfunction / protection function

3.1 sensor malfunction protection

1?when indoor ambient temp. sensor and outdoor temp. sensor are short circuit or open circuit,the unit displays malfunction code,the total units stop running;

2?when inlet and outlet temp. sensor of indoor evaporator appears malfunction for DC inverter single-split series,the unit runs with fault and sends the middle part of indoor coil temperature to outdoor unit;

3?when inlet and outlet temp. sensor of indoor evaporator appears malfunction for DC Inverter Multi-Split Air-Conditioner Unit,the current indoor unit will shut down and display the relevant malfunction code?

3.2 communication error protection

If the communication is abnormal for continuous 3min,the system will stop the compressor and display the relevant malfunction code?When the communication is normal and fault code disappears for 1 minute , the system will automatically start?

3.3 PG motor protection function

If the system checks the PG motor has not the feedback signal for continuous 20 seconds in the PG motor running,the PG motor will enter the running within fault;if the system checks the speed of PG motor is lower than 200rpm for continuous 60 seconds,thus the system considers PG motor faulty ,and then the total units stop running and report the relevant malfunction code?

The following is the setting motor speed during operation within fault:

(1) the system will break-over controlled silicon after zero passage 1mS in the high wind;

(2) the system will break-over controlled silicon after zero passage 2mS in the mid wind;

(3) the system will break-over controlled silicon after zero passage 2.5mS in the low wind;

(4) the system will break-over controlled silicon after zero passage 3mS in the slightly wind;

if the feedback signal returns to be normal during PG motor operation within fault,the PG motor still runs within fault,until the system starts again next time?

remark: there is not PG motor protection function in producing self-check?

3.4 indoor coil pipe antifreeze protection in cooling

(1) when indoor coil pipe temperature is less than 6? in cooling,the compressor doesn't run?

(2) when indoor coil pipe temperature is less than 1?,the system stops compressor and displays indoor coil pipe overcooling/overheating protecting code;

(3) when indoor coil pipe temperature is less than 3?,the compressor's frequency will drop,until lowest running frequency,thus the compressor stops running and the system displays indoor coil pipe overcooling/ overheating protecting code ;

(4) when indoor coil pipe temperature is greater than or equal to 3?, but is less than 6?,compressor frequency forbids rising;

(5) when indoor coil pipe temperature is greater than or equal to 6?,the system runs normally;

(7)after this protection code appears for 1 minute,the system could start automatically?

3.5 indoor coil pipe overheating protection in heating

(1) when indoor coil pipe temperature is greater than or equal to 48? in heating,the compressor doesn't run;

(2) when indoor coil pipe temperature is greater than or equal to 73?,the compressor stops running and the system displays indoor coil pipe overcooling/overheating protecting code;

(3) when indoor coil pipe temperature is greater than or equal to 63?,the compressor's frequency will drop,until lowest running frequency,thus the compressor stops running and the system displays indoor coil pipe overcooling/ overheating protecting code ;

(4) when indoor coil pipe temperature is greater than or equal to 52?, but is less than 63?,compressor frequency forbids rising;

(5) when indoor coil pipe temperature is less than 52?,the system runs normally;

(6) after this protection code appears for 1 minute,the system could start automatically?

3.6 system lacking refrigerant or 4-way valve fault

(1) during cooling:

After the compressor has operated for five minutes (which has been set in the EEPROM), if the temperature of the indoor coil can not be 5? lower than the room temperature, the indoor fan will automatically turns to the breeze operation, 13 minutes later, if above requirements can not been met with, the compressor will be stopped to display the fault code; it can only operate again after switching off.?

(2) during heating:

When the temperature of the indoor coil is lower than 20? (which is set in the EEPROM) for 20 minutes, the compressor will be stopped to display the fault code; it can only operate again after switching off.?

The system fault can only be determined within 20 minutes after the compressor is switched on, after that the faults will not be determined. After stopping in remote controlling or emergency or power off, the system fault should be determined within 20 minutes after starting on again. After the system fault occurs, the indoor fan will not work, and the flap will not be closed.?

Appendix?:malfunction and protection display

1.Indoor fault and protection explanation

(1) when the indoor unit has not the nixietube,the malfunction and protection can display by LED lamp:firstly light 3 seconds,then flicker n at 1Hz,looping execution;

(2)when the indoor unit has the nixietube:

a) the nixietube shows "dF" code in defrosting;

b) under normal circumstances,the nixietube only shows the latest malfunction code or protection code;

(3) when malfunction and protection exist at the same time, the unit will shut down .but the system is priority to showing malfunction code?

2.Indoor unit fault display table

Check parts Serial number Malfunction content Indoor unit display status nixietube LED(indoor unit without the nixietube) Running lamp

Flashing frequency n Timing lamp

Flashing frequency n Indoor parts 1 The communication faults in the indoor and outdoor units F1 1 Lighten 2 Indoor ambient temp. sensor fault F2 2 Lighten 3

Indoor coil temp. sensor fault

(include:inlet?middle of pipe?outlet) F3 3 Lighten 4 Indoor fan fault F4 4 Lighten Outdoor parts 1 Outdoor module fault F5 5 Lighten 2 Outdoor ambient temp. sensor fault F6 6 Lighten 3 Outdoor coil temp. sensor fault F7 7 Lighten 4 compressor suction temp. sensor fault F8 8 Lighten 5 compressor discharge temp. sensor fault F9 9 Lighten 6 inductor of current or voltage fault FA 10 Lighten 7 compressor drive abnormal fault FC 11 Lighten 8 Power supply phase lacking or phase sequence fault FD 12 Lighten 9 Return-air sensor abnormal

(include these roads A?B?C?D) FE 13 Lighten 10 Others fault FF 14 Lighten 11 Outdoor DC fan fault FH 15 Lighten

3.Indoor unit protection display table

Check parts Serial

number Protection content Indoor unit display status nixietube LED(indoor unit without the nixietube) Running lamp

Flashing frequency n Timing lamp

Flashing frequency n Indoor parts 1 Evaporator temp. protection P1 Lighten 1 Outdoor parts 1 overheat, over current protection of inverter module P2 Lighten 2 2 over current protection P3 Lighten 3 3 Compressor discharging temp.protection P4 Lighten 4 4 over heat of compressor top protection P5 Lighten 5 5 suction temp. of compressor protection P6 Lighten 6 6 power supply overcurrent / overvoltage protection P7 Lighten 7 7 low presser of gas return protection P8 Lighten 8 8 high pressure of discharge protection P9 Lighten 9 9 high temp. of condenser protection PA Lighten 10 10 high temp. of outdoor ambient protection PC Lighten 11 11 system lacking fluorine or reversing valve protection PH Lighten 12 12 Other protection PF Lighten 13

Appendix?: display lamp panel

Note:when the system electrifies at first time,all the patterns on display lamp panel and LED lamp all lighten,and extinguish after 2s.

Display modes of two LED-indicating lamps and double-8-LED

(1) Running lamp: Lightened when starting-up with power on, extinguished when turning off, flash at the frequency of one time /one second in the mode of anti-cooling air.?

(2) Timing lamp: lightened during timing condition, extinguishing in other conditions.?

(3) Display of the digital tube:

a) The digital tube displays the set temperature of the air conditioner under the normal condition.;

b) When the user has set the timed turning on or off, the digital tube will display the time of the timed turning on or off, after the time has been set, it will return back to display the set temperature after the set time flashes for five seconds.;

c) Only the remaining time is displayed at the time of timed turn on.;

d) Only the "dF" is displayed during defrosting.;

e) The faults or protection codes are displayed at the time of the faults or protection.?

VI?Failure display

LED running lamp(flicker times) timer lamp(flicker times) Fault content The reason of fault and solution F1 1 light communication fault 1?Check whether the connection of the outdoor unit and indoor unit is one to one, otherwise connect the L, N and communication line of the indoor unit and outdoor unit one to one.

2?Measure whether the voltage between the zero line and the communication line is 18V-30AC half-wave signal, check whether the communication circuit on the indoor and outdoor electric control board has been damaged, otherwise replace it.

3?Check whether the LED on the outdoor power board has been on, otherwise replace the electric control board.

4?Check whether the unit is abnormal caused by the external interference, if it is, then find the interfering source, and removes it. F2 2 light The indoor ambient temp. sensor fault 1?Check whether the resistance of sensor is normal, otherwise replace it.

2?Check whether the sensor wire is short circuit or open circuit, and whether the plug is well contacted, whether there is welding off or rosin joint on the electric control board, repair it if there is any above.

3?When the 1 and 2 are both normal, then the components or integrated circuit is damaged, the electric control board should be replaced. F3 3 light The coil pipe temp. sensor of indoor unit fault(include :inlet, middle, outlet) 1?Check whether the resistance of sensor is normal, otherwise replace it.

2?Check whether the sensor wire is short circuit or open circuit, and whether the plug is well contacted, whether there is welding off or rosin joint on the electric control board, repair it if there is any above.

3?When the 1 and 2 are both normal, then the components or integrated circuit is damaged, the electric control board should be replaced. F4 4 light indoor fan fault 1? Check whether the contact of the plug of the motor wire and socket is well, making sure well contact.

2?Check whether the indoor motor has damaged, the motor should be replaced when it is damaged.

3?Check whether the controllable silicon and other components on the electric control board have damaged, replace the controllable silicon or electric control board when they are damaged.

F5 5 light module of outdoor unit fault

1?Check whether the connection of the compressor is reliable, otherwise connect firmly again.

2?Check whether the fixation between the IPM module and the radiator is firm.

3? Check whether the compressor is well, otherwise replace it.

4? Check whether the IPM module is abnormal, otherwise replace it. F6 6 light The outdoor ambient temp. sensor fault 1?Check whether the resistance of sensor is normal, otherwise replace it.

2?Check whether the sensor wire is short circuit or open circuit, and whether the plug is well contacted, whether there is welding off or rosin joint on the electric control board, repair it if there is any above.

3?When the 1 and 2 are both normal, then the components or integrated circuit is damaged, the electric control board should be replaced. F7 7 light The outdoor unit coil pipe temp. sensor fault 1?Check whether the resistance of sensor is normal, otherwise replace it.

2?Check whether the sensor wire is short circuit or open circuit, and whether the plug is well contacted, whether there is welding off or rosin joint on the electric control board, repair it if there is any above.

3?When the 1 and 2 are both normal, then the components or integrated circuit is damaged, the electric control board should be replaced. F8 8 light The compressor suction temp. sensor fault 1?Check whether the resistance of sensor is normal, otherwise replace it.

2?Check whether the sensor wire is short circuit or open circuit, and whether the plug is well contacted, whether there is welding off or rosin joint on the electric control board, repair it if there is any above.

3?When the 1 and 2 are both normal, then the components or integrated circuit is damaged, the electric control board should be replaced. F9 9 light The compressor discharge temp. sensor fault 1?Check whether the resistance of sensor is normal, otherwise replace it.

2?Check whether the sensor wire is short circuit or open circuit, and whether the plug is well contacted, whether there is welding off or rosin joint on the electric control board, repair it if there is any above.

3?When the 1 and 2 are both normal, then the components or integrated circuit is damaged, the electric control board should be replaced. FA 10 light inductor of current or voltage fault 1?Check whether inductor of current or voltage have been damaged, they should be replaced if they are fault. FC 11 light compressor drive fault 1?Power on again, and check the operation of the compressor is normal.

2?Check whether the connection of the compressor is reliable, otherwise repair.

3?Check whether the components on the electric control board have been damaged, if they are damaged, the components or the electric control board should be replaced. FE 13 light gas return sensor fault(include :A,B,C,D pipe road) 1?Check whether the resistance of sensor is normal, otherwise replace it.

2?Check whether the sensor wire is short circuit or open circuit, and whether the plug is well contacted, whether there is welding off or rosin joint on the electric control board, repair it if there is any above.

3? When the 1 and 2 are both normal, then the components or integrated circuit is damaged, the electric control board should be replaced. FF 14 light other fault 1 check whether the system pressure is normal, whether to have the broken tube result in the leakage of refrigerant.

2 check whether the indoor coil temperature sensor is installed in place.

3 check whether the four-way valve runs abnormally.

P1 light 1 The evaporator temp. protection

1?Check whether the filter of indoor unit is too dirty, and it should be cleaned when it is too dirty.

2?Check whether it has barrier around indoor unit, it should be remove if it has.

3?Check whether the indoor motor is damaged, it should be replaced motor or electrical control board when it is damaged. P2 light 2 overheat, over current protection of inverter module 1?Check whether the fixation between the IPM module and the radiator is firm.

2?Check whether the compressor is well, otherwise replace it.

3? Check whether the IPM module is abnormal, otherwise replace it. P3 light 3

AC input current over large protection 1?Check whether the ambient temperature exceeds the operation range for the air conditioner

2?Check whether the current detection circuit is abnormal, the electric control should be replaced when it is abnormal. P4 light 4 The discharge temp. of compressor protection 1?Check whether the air condition system and pressure are normal.

2?Check whether the sensor, connecting wire of the sensor and the detection circuit are abnormal. P6 light 6 The suction temp. of compressor protection 1? Check whether the air condition system and pressure are normal.

2? Check whether the sensor, connecting wire of the sensor and the detection circuit are abnormal. P7 light 7 low or high voltage protection 1?Check whether the supply voltage is out of rang from 150 to 270V

2?Check the voltage detection circuit of the IPM base board is abnormal, if it is abnormal, the IPM base board or the electric control board should be replaced. P8 light 8 low presser of gas return protection 1?Check whether the pressure is normal when the unit is running, if it is abnormal, should detect the leakage and welding? add refrigerant. P9 light 9 high pressure of discharge protection 1? Check whether the pressure is normal when the unit is running, if it is abnormal, should detect the leakage and welding? add refrigerant. PA light 10 The evaporator coil high temp. protection 1?Check whether the condenser of outdoor unit is too dirty, and it should be cleaned when it is too dirty.

2?Check whether it is running at bad condition long time.

3?Check whether senor and wire are normal. PC light 11 The outdoor ambient high temp. protection 1?Check the outdoor ambient temperature is too high or there is heat source around the outdoor unit.

2? Check whether the sensor and sensor wire are normal. PH light 12 Lack the refrigerant or reversal valve protection 1?check whether the system pressure is normal, whether to have the broken tube result in the leakage of refrigerant.

2?check whether the reversal valve runs abnormally.

VII?Reference of the fault code and detecting methods for inverter

Please note: this operation guidance is for maintenance reference only, it can be different from the units you order.

A?F1 (Communication fault) the possible reasons and detecting measures:

1. First, check whether the wires of the indoor and outdoor terminal boards are wrong connection or poor connection.

2. Check whether the alternating current of the outdoor PCB is normal, or whether the fuse is loosened or blew out.

(the input voltage of the outdoor terminal) (the input voltage of the Bridge rectifier)

(the fuse can be gotten through under the normal situation. Change the fuse if it is open circuit.)

3. Check whether the voltage of the DC PN is normal. The normal voltage should be around 300V.

(the output voltage of the Bridge rectifier) (the output voltage of the PN)

4. Check whether the input power cord or the output power cord is mistakenly connected in the controller board.

5. Check whether the communication voltage between the N and S is normal. Use the AC voltage gear to measure the voltage. If it changes from several volts to scores of volts, it means the communication voltage is normal.

6. Check whether the bridge rectifiers are damaged

(The forward resistance of every diode in the bridge rectifiers should be around 500?)

(remove one terminal when measuring the output resistance of the bridge rectifiers (the AC input resistance of the bridge rectifier should be infinite)

7. Check whether the electrolytic capacitor is convex or burned out.

8. Check whether the IGBT is damaged

;

9. Check whether the relative electronic components are burned out or loose weld by eyeballing.

10. Check whether the external environment exists the source of the strong electromagnetism, which may cause disturb.

11. If the above procedures cannot solve the problem, please change the outdoor whole set of the electric control boards.

B.F2(Room Temperature sensor fault) F3(Indoor coil exit temperature sensor fault,Indoor coil entry temperature sensor fault or Indoor coil mid point temperature sensor fault)

1. Measure the resistance of the temperature sensor and check it referring to the resistance table. Check if the resistance has a serious deviation to the table.

(the environment temperature is about 32 degrees centigrade)

2. Check whether the inserter or the wires of the sensor are damage by eyeballing.

3. Check whether the sensor's circuit in the electronic control board is loss weld or damaged.

4. If the above procedures cannot solve the problem, please change the indoor electric board.

C?F4: fault of PG fan motor

1? Check whether the contacted terminal of the fan motor is loose.

2? Check whether the startup winding and running winding of the fan motor is broken (open circuit or short circuit)

3? Check whether the fan motor or the blade of it is blocked.

4? Check whether the indoor PCB is faulty (no signal output of the fan motor)

D?F6 fault of the outdoor sensor

1?Measure the resistance of the sensor and check up with the temperature-resistance table, and see if there is a great departure with the resistance.

2?Check whether the contactor and the circuitry is well

3?Check whether there is loose weld or damage of the sensor circuit part, situation like rupture which the finger points at in the following picture:

4? If the above procedures cannot solve the problem, please change the indoor PCB.

E?FC fault of the outdoor drive and failure of the compressor startup

1?Drive module burns out, that is short circuit between P?U?V?W?N terminal.

(Normal forward resistance between P terminal and U,V,W,N terminal should be 380-450?)

(Normal voltage between U terminal and V,W terminal should be 170-270V)

2?Check whether the U,V,W terminals is contacted well

3?Check whether the compressor winding is burnt out.

(Normal resistance of the three windings should be the same and probably equal to 1?)

5?Check whether the compressor is blocked. If blocked, please try to beat the compressor with rubber stick slightly.

F?dI mode conflict or not allowed

We suggest you reset the running mode (cold or heat), and make sure all the indoor units are running in the same mode.

G? dF: defrost

1?Under the heat mode, it's a normal display of defrosting.

2?Under other mode except heat, if there is a dF code, perhaps the anti-jamming capacity of the inductance is too weak which leads to a misinformed faulty code. Please check whether there is a magnetic ring on the connecting pipe of the indoor and outdoor units.

H? P2:fault of the outdoor inverter module protection

1?Check whether the connection of the compressor is reliable. If not, please make it firmly enough.

2?Check whether the fixation between the IPM module and the radiator is firm.

3?Check whether the compressor is well. If not, please replace it.

4?Check whether the IPM module is normal. If not, please replace it.

I?P3 ac current input of the outdoor unit is too large

1?Check whether the ambient temperature exceeds the operation range of the air conditioner

2?Check whether the current detection circuit is abnormal. The electric control should be replaced if it is abnormal.

3?Check whether the outdoor fan motor is broken or not, following is the test method of ac outdoor motor:

4? If the above procedures cannot solve the problem, we suggest changing the inductance.

J? P4 discharge temperature of the outdoor compressor is too high, the outdoor ambient temperature is too high, temperature switch of compressor shell is breaking, the module is over temperature

1?Check whether the pressure is normal when the unit is running. If abnormal, should detect the leakage and welding, and then add refrigerant.

2? Check whether outdoor ambient temp. is too high or too low, when the temp. is more than -20 degree and less than 55 degree, it can disappear automatically.

3?Communicate interference. Earth wire and communicate wire can't put in one cable.

4?Check whether temp. switch of compressor is damage, it should be replace if it's damaged.

K? P7 dc generatrix voltage of outdoor unit is abnormal

1?Check whether the power supply voltage is out of rang from 150 to 270V

2.?Check the voltage detection circuit of the IPM base board is abnormal, if abnormal, the IPM base board or the electric control board should be replaced.

L? P8: gas leakage or fault of the selector valve

1?Check whether the high and low pressure valves have been opened. If not, please open the valves.

2?Check whether the indoor coil pipe temperature sensor is normal. If abnormal, the sensor should be replaced.

3?Check the system pressure is normal. If abnormal, should detect leakage repairing, welding and add the refrigerant

4?Check whether the coil resistance of the electric expansion is normal and the valve body is open completely.

5?Check and listen if the sound of 4-way selector valve is crisp.

VIII .User's Manual For Split Wall-Mounted Air Conditioner

Please read the user's manual carefully before using the product

Instructions to users

The name of each part and its function

Indications of unit

Remote controller

Use of remote controller

Operating machine in selected modes

Basic principles and performances

Features of Heating Operations

Methods of maintenance